How many lux in an office, school and shop in Latvia

Roberts Mačeks · 28 November 2026 · Latviešu versija

These are Latvian requirements. The figures below come from Latvian Cabinet Regulations and the Latvian edition of the European standard (LVS EN 12464-1). Lithuania and Estonia have their own rules — see the Lithuanian and Estonian articles. Other countries may differ too.

The short answer for Latvia: 500 lx at an office desk, 300 lx in a classroom, 300 lx on a shop floor, 500 lx at a checkout, 100 lx in a corridor. Below are the tables, the sources, and what else to check so that the lighting is not only compliant but also comfortable.

What a lux is

A lux (lx) tells you how much light falls on a surface: 1 lx is 1 lumen per square metre. A luminaire's lumens tell you how much light it emits; lux tells you how much of it reaches the desk, the floor or the shelf. That is why the same luminaire gives more lux in a low, light-coloured room than in a tall, dark one.

Where the Latvian figures come from

Office

Room or taskEm, lxUoUGR ≤Ra ≥
Writing, reading, data processing5000.601980
Technical drawing7500.701680
Meeting and conference rooms5000.601980
Reception, customer service3000.602280
Archives2000.402580

Em from Regulation No. 359, Annex 2, item 25. Regulation No. 359 also requires lighting in meeting rooms to be adjustable. Uo, UGR and Ra from LVS EN 12464-1.

Schools and kindergartens

RoomEm, lxSource
Classroom (on the desk)300No. 610
Board, centre (vertical)500No. 610
Sports hall300No. 610
Assembly hall200No. 610
Evening and adult education classrooms500No. 359
Lecture halls, auditoriums500No. 359
Kindergartens, play rooms300No. 359

Regulation No. 610, Annex 3, and Regulation No. 359, Annex 2, item 34. In classrooms and lecture halls the lighting must be adjustable. For classrooms LVS EN 12464-1 also gives Uo ≥ 0.60, UGR ≤ 19 and Ra ≥ 80.

Shops and shared areas

RoomEm, lxUoUGR ≤Ra ≥
Sales area3000.402280
Checkout, packing desk5000.601980
Storage room (200 lx if in continuous use)1000.402560
Corridors, traffic routes1000.402840
Stairs1500.402540
Toilets, changing rooms1000.402580
Canteen2000.402280

Em from Regulation No. 359, Annex 2. Uo, UGR and Ra from LVS EN 12464-1:2021, which recommends 200 lx for toilets.

The requirement is a minimum for the whole service life

The values are minimums — the level the lighting must not fall below, even when the luminaires have aged and got dirty. A new installation therefore has to deliver more. Lighting designers account for this with a maintenance factor: with a factor of 0.8, an office that needs 500 lx should be designed for about 625 lx when new. The exact factor depends on the luminaire, how clean the room is and how often it is maintained.

Lux alone is not enough

A room can meet the lux requirement and still be tiring if the light is uneven or glaring.

UGR (glare) in more detail

Glare is what you feel when a luminaire or its reflection is in your field of view and your eyes tire, even though there is enough light. UGR (Unified Glare Rating) expresses it as one number. The scale usually runs from 10 to 28 in steps of 3: the lower the number, the less glare.

UGR ≤Where it is requiredIn practice
16technical drawing, very fine workyou hardly notice the luminaires
19office, classroom, checkoutfine for a full day at a screen
22sales area, reception, productionnoticeable, but fine for short tasks
25storage, archives, stairsfine to pass time in, not for long work
28corridorsonly for walking through

Example. An office ceiling has 600 × 600 mm LED panels. With an opal (milky white) diffuser the bright surface is visible from every angle, and the room's UGR often ends up above 19. The same panel with a microprismatic diffuser or a louvre sends more of its light downwards and looks less bright from the desk, so UGR drops below 19. The lux on the desk can be almost the same in both cases.

What else reduces glare:

The UGR on a manufacturer's data sheet is usually for a standard room (for example 4H × 8H, reflectances 70/50/20). It is good for comparing luminaires, but the UGR of a real room has to be calculated from its dimensions, layout and viewing direction.

Ra (colour rendering) in more detail

Ra (also called CRI) shows how natural colours look under a light compared with a reference light — daylight or an incandescent lamp has Ra 100. It is measured on 8 pastel test colours (R1–R8) and averaged.

Ra ≥Enough for
40corridors, stairs, where colours do not matter
60storage, rough work
80offices, schools, shops, kitchens — almost every workplace
90medical examination, colour matching, clothing and cosmetics shops, galleries, hairdressers

Example. In a meat counter under a luminaire with Ra 80 the meat can look greyish and customers pass it by. With Ra 90+ and good red rendering it looks fresh. The same goes for skin tone at a bathroom mirror: with low Ra, skin looks pale or greenish.

Two things that are often mixed up:

And at home?

Latvia has no mandatory lux requirements for homes. In practice people aim for 100–300 lx in a living room, 50–150 lx in a bedroom, 300–500 lx on a kitchen worktop, 300–500 lx at a bathroom mirror, and 500 lx at a home desk, the same as in an office.

How to check

In a finished room, lux is measured with a lux meter at work-surface height, at several points, so that uniformity shows too. Phone apps are only good for a rough idea. Before installation the same can be calculated from the manufacturer's photometric file (LDT or IES), the room dimensions and the surface reflectances.

See the lux before you buy. The early demo version of Q-Space PLS shows a room in 3D with real luminaires from Baltic manufacturers and a lux map on the desk and floor. Open the catalogue or write to [email protected].

Sources

  1. Cabinet Regulation No. 359 of 28 April 2009 “Darba aizsardzības prasības darba vietās” (Labour protection requirements in workplaces), Annexes 2 and 3 — likumi.lv (in Latvian).
  2. Cabinet Regulation No. 610 of 27 December 2002 (hygiene requirements for schools), Annex 3 — likumi.lv (in Latvian).
  3. LVS EN 12464-1:2021 “Light and lighting — Lighting of work places — Part 1: Indoor work places”.